CYATS2-80 Rail type automatic transfer switch is a PC class infrequent change-over switch, with two-station design (commonly used for A and standby for B), suitable for AC systems with AC 50-60hz and rated current 6A-63A. The main function of the automatic transfer switch is when the main power (common power supply A) fails, the ATS will automatically switch to the backup power (Backup power supply B) to continue working (switching speed <50 milliseconds), which can effectively solve the troubles caused by power outages.
When both A and B have electricity, priority is using A Power
NOTE:
1. Manual/automatic operation can ensure the opening and closing performance of electrical operation, but in manual operation , there is no guarantee due to the different _opening/closing speeds of the operators. In manual operation, there’s possible for excessive silver alloy loss . Therefore, the selector switch should only be pulled to the manual position after all power has been cut off for inspection and maintenance of the operating system and contact information.
2, Normally, pull the selector switch to the electric position. When manual operation is required, pull the selector switch to the manual position. After manual operation is complete, pull the selector switch from the manual position to the automatic position.
The control circuit TSE is immediately energized. After the change over is completed, the internal switch will damage the coil in the control circuit, and the coil can work normally at 85%-110% of the rated operating voltage. Too low input voltage may cause the coil to overheat and burn out.
Attention!When manual operation the mode selection switch must be in “manual” position
Case grade | 63 |
Rated operating curent le(A) | 6A/10A/16A/20A/25A/32A/40A/50A/63A |
Rated insulation voltage Ul | 690V |
Rated impulse withstand voltage Uimp | 8kV |
Rated working voltage Ue | AC220V/AC110V |
Rated frequency | 50/60Hz |
Class | PC class: can be switched on and loaded without generating short-circuit current |
Polenumber | 4P |
Rated short-circuit current Iq | 50kA |
Contactor change-overtime | <50ms |
Operation change-over time | <50ms |
Return change-over time | <50ms |
Power off time | <50ms |
Change-over operation time | <50ms |
Mechanical life | ≥8000 times |
Electrical life | ≥1500 times |